Power-Plume®, with curb, with a fan
Power-Plume®, with curb, with a fan
AMCA Air Cert. logo
Certifications, vary by model
Vari-Plume®
U.S. Patent No. 7,484,929
A high plume fans, designed for safer and more reliable displacementof lab exhaust air.
This schematic represents a typical lab exhaust system. Included are the lab hoods, modulating control valves, ductwork connecting to a manifold, a mixing box with bypass damper, a QMX mixed flow fan and a Vari-Plume high plume dilution nozzle. While this illustration shows a single fan/multiple hood arrangement, the Vari-Plume is also available for other lab exhaust configurations. From a one fan/one hood system to more critical redundant system configurations, Vari-Plume is your answer for laboratory exhaust. Multiple fan system options for both the QMX and CA are available.
AMCA Air & Sound Certified for Induced Flow Fan
Performance
LE Series
Standard Nozzle, without power. Can be added onto several exhaust fans
Power-Plume®
U.S. Patent No. 8,672,614
The Power-Plume was designed for critical lab applications where safety and efficiency are the primary concerns.
Power-Plume is a powered induction device used to induce large amounts of ambient air and generate plume height regardless of the lab exhaust flow. This device has the unique advantage of maintaining a minimum 50 foot plume height even as the lab exhaust flow is reduced for partial load conditions. Dilution rates at maximum lab exhaust flow exceed 200%. As the lab exhaust is reduced, dilution rates can exceed 1,000%.
Power-Plume conveys a column of ambient air around the lab exhaust air encapsulating the contaminated lab exhaust. The primary lab exhaust fan is still utilized to exhaust the contaminated lab air. It can now be operated on a VFD for partial load conditions. This saves energy as we no longer need to utilize bypass air during partial load conditions to maintain plume height. Since the primary lab exhaust fan is not required to generate the high discharge velocities for adequate plume height, the power requirements of this fan are significantly reduced.
Related Documents
Vari-Plume® Catalog
TCNHBLE Data Catalog
QMXVP Data Catalog
CAVP Data Catalog
Power-Plume ® Catalog
Laboratory Exhaust Manual
Power Plume ® Manual
TCN Manual
QMX Manual
CA Manual
QMX EZ Out Belt Drive Supplement
QMX EZ Out Direct Drive Supplement
See the Downloads tab for specifications, submittals and FanDrafter files
See also QMX: Mixed-Flow Blowers
See also CA / CF: Steel Centrifugal Blowers
See also TCN: Tubular Centrifugal Inline Fans
See also CP: Steel and Aluminum Vent Sets
TCNHBLE
QMX-VP
CA-VP
CPS-LE
PP
Downloads
AC
LOREN COOK COMPANY certifies that the TCNHBLE shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
Type TCNHBLE is furnished standard with UL 705 and cUL 705 listings (Power Ventilator/ZACT).
TCNHBLE
Laboratory Exhaust
Tubular Centrifugal
Belt Drive
Backward inclined, non-overloading welded Aluminum wheel
Minimum 12 gauge steel welded housing
AMCA type “B” Spark resistant construction
High velocity discharge cone
Phenolic epoxy powder with UV protection (Light Gray)
L10/100k concentric locking regreasable bearings
Large bolted access door – Allows wheel and bearing replacement
Lifting lugs
Fan Drain
Weather cover
Reinforced curb cap
Stainless Steel shaft
Stainless Steel hardware
Stainless Steel lube lines
NEMA 3R disconnect mounted and pre-wired
1.5 Service Factor drives
Designed to withstand 125 mph wind
High Plume Blowers
Suggested Specification Section 15500 (Master Format™ 1996)
Suggested Specification Section 23 38 16 (Master Format™ 2004)
PART 1 GENERAL
1.01 WORK INCLUDED
High Plume Laboratory Exhaust Fans
1.02 RELATED WORK
All sections, drawings plans, specifications and contract documents.
1.03 REFERENCES
AMCA Publication 99, “Standards Handbook” (2003 Edition)
AMCA Standard 210-99, “Laboratory Methods of Testing Fans for Aerodynamic Performance Rating”
AMCA Standard 211-05, “Certified Ratings Program- Product Rating Manual for Fan Air Performance”
AMCA Standard 300-96, “Reverberant Room Method for Sound Testing of Fans”
AMCA Publication 311-05, “Certified Ratings Program – Product Rating Manual for Fan Sound Performance”
AMCA 204-96, “Balance Quality and Vibration Levels for Fans”
AMCA 500-D-98, “Laboratory Methods of Testing Dampers for Rating”
AMCA 500-L-99, “Laboratory Methods of Testing Louvers for Rating”
SMACNA “HVAC Duct Construction Standards – Metal and Flexible”, Medium Pressure Plenum Construction
ANSI/AIHA Z9.5-2003, “Laboratory Ventilation”
ANSI/ABMA 11-1990 (R1999), “Load Ratings and Fatigue Life for Roller Bearings”
ASHRAE, “Laboratory Design Guide” (2002 Edition)
ASTM B117-03, “Standard Practice for Operating Salt Spray (Fog) Apparatus”
ASTM D2247-02, “Standard Practice for Testing Water Resistance of Coatings in 100% Relative Humidity”
ASTM D2794-93(2004), “Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact)”
QUALITY ASSURANCE
Performance ratings: Fans shall be licensed to bear the AMCA Certified Ratings Seal for Sound and Air Performance. Acceptable manufacturers whose equipment is not licensed to bear the AMCA Certified Ratings Seal for Sound and Air Performance shall submit sound and air performance data obtained and calculated in accordance with AMCA Standards 210, 211, 300, and 311. These tests shall be performed by a laboratory that is accredited by AMCA.
Fans shall be manufactured at an ISO 9001 Certified facility.
Units specified as Spark Resistant Construction shall conform to AMCA Standard 99-0401-86, “Classifications for Spark Resistant Construction.”
Fan impeller shall be statically and dynamically balanced in accordance with AMCA Standard 204-96, “Balance Quality and Vibration Levels for Fans.” Vibration tests shall be conducted and recorded on each assembled fan before shipment at the specified fan RPM. These readings shall conform to the AMCA 204-96 Standard.
Fan manufacturer shall provide at the owner and engineer’s expense and option, witness testing of the fan in an AMCA Accredited Laboratory during the submittal stage of the project. These tests shall be performed in accordance with AMCA Standard 210-99, “Laboratory Methods of Testing Fans for Aerodynamic Performance Rating.”
SUBMITTALS
Provide dimensional drawings, product data and performance on each high-plume dilution laboratory exhaust fan unit.
Provide fan curves for each fan at the specified point of operation. Airflow, static pressure and brake horsepower shall be clearly shown on the submittal. Fan curves submitted for review not utilizing a “one to one” (same scale for horizontal and vertical axis) scale shall be rejected. For multiple fan assemblies, fan curves shall also be adjusted to show assembly operation.
Primary airflow from laboratory exhaust system, optional bypass airflow through mixing box, overall airflow through fan, and discharge nozzle airflow shall be provided. Outlet nozzle velocity and plume rise calculated per ASHRAE Applications Handbook shall also be provided for the specified fan performance and wind velocity.
PART 2 PRODUCTS
2.01 GENERAL
Fan performance data shall follow AMCA Standard Conditions of 0 Ft elevation and 70 Deg F. (Air Density shall be 0.075 lb/ft)
Fans selected shall allow for +/- 15% variation of scheduled static pressure and airflow.
Fan shall be AMCA Arrangement 9, Belt Drive, Upblast Inline Centrifugal Blower as dictated on the plans and specifications.
Fan systems shall incorporate integral lifting lugs for ease of installation.
2.02 FAN HOUSING AND CONSTRUCTION
Fan housing shall be a minimum 12 gauge steel construction.
Adjustable motor plate, where applicable shall utilize threaded studs for positive belt tensioning.
Fan shall be constructed with an integral housing drain to alleviate rainwater.
Fan shall contain a bolted and gasketed access door. Access door shall allow for the removal of wheel, shaft and bearings without the removal of the fan from the laboratory exhaust system.
Belt driven fan shafts shall be stainless steel and accurately turned, ground and polished. Shafting shall be sized for a critical speed of at least 125% of maximum fan RPM.
Unit fasteners exposed to corrosive airstream shall be of stainless steel construction.
Option1 Unit components fabricated of steel shall be coated with an electrostatically applied, high performance, baked phenolic epoxy powder coating with an ultraviolet protective topcoat. Finish color shall be light gray. Coating thickness shall be 5.0 mils.
Option2 Unit components fabricated of steel shall be coated with an electrostatically applied, baked epoxy powder coating with an ultraviolet protective topcoat. Finish color shall be dark gray. Coating thickness shall be 5.0 mils.
Option3 Unit components fabricated of steel shall be coated with an electrostatically applied, baked polyester powder coating. Finish color shall be gray. Coating thickness shall be 2.0 mils.
Coating shall be salt spray tested per ASTM B117 for in excess of 1000 hours without failure, humidity resistance tested per ASTM D2247 for in excess of 1000 hours without failure, and impact resistance tested per ASTM D2794 and shall pass a minimum of 100 in-lbs.
Unit shall bear an engraved aluminum nameplate. Nameplate shall indicate design CFM, static pressure, and maximum fan RPM.
Units specified as Spark Resistant Construction shall be constructed to the AMCA Spark Resistant Construction level as dictated on the plans and specifications.
Unit shall be shipped in ISTA Certified Transit Tested Packaging.
HIGH PLUME DISCHARGE NOZZLE
Fans shall incorporate a conical discharge nozzle supplied by the fan manufacturer.
Discharge nozzle shall be constructed and designed to efficiently handle up to 6000 feet per minute outlet velocity. Nozzle shall not utilize a stack cap nor hinged cover and shall be matched to project specific requirements as noted on the contract drawings.
2.04 CENTRIFUGAL FAN IMPELLER
Fan impeller shall be non-overloading, steel centrifugal, backward inclined, flatblade type. Blades shall be continuously welded to the backplate and deep spun inlet wheel shroud.
Fan impeller hub shall be keyed and securely attached to the fan shaft.
Fan impeller shall be statically and dynamically balanced in accordance with AMCA Standard 204-96, “Balance Quality and Vibration Levels for Fans.”
Fan impeller shall be coated with a finish to match the fan housing.
Fan impeller shall be balanced utilizing weights which are welded and coated with chemical resistant coating. Balancing by means of bolts and washers shall not be acceptable.
Belt driven fan bearings shall be designed and tested specifically for use in air handling applications. Construction shall be heavy duty regreaseable ball or roller type in a cast iron pillow block housing utilizing concentric mounting locking collars.
Option1 Belt driven fan bearings shall be selected for a minimum L50 life of not less than 200,000 hours.
Option2 Belt driven fan bearings shall be selected for a minimum L10 life of not less than 200,000 hours.
Belt driven fan units shall have stainless steel lube lines installed from the fan bearings with Zerk fittings to allow for easy lubrication.
2.05 BYPASS AIR PLENUM
For constant volume systems the fan and nozzle assembly shall be directly connected to the roof curb and exhaust duct.
For variable volume systems a bypass air plenum shall be supplied as shown on the contract drawings.
Bypass air plenum shall be designed to support fan assembly (assemblies) and configuration(s) as shown on the contract drawings.
Bypass air plenum shall introduce outside air above the roof level and shall have rain hood(s) and bird screen protection over the bypass air damper(s).
Bypass air plenum shall be constructed of welded steel, minimum 14 gauge, with a finish to match the fan housing.
Bypass dampers shall be opposed blade low leakage design. The dampers shall be aluminum construction and coated to match the fan housing.
Option1 Extended shafts and manual locking quadrant handles shall be provided for adjustment of the dampers. The extended shaft can be used for external connection to actuators by controls contractor.
Option2 24V electric actuators shall be provided to control the dampers. The actuators shall be provided by the fan manufacturer.
Fan isolation dampers shall be provided as shown on the project documents.
Option1 Isolation dampers shall be gravity type coated to match fan housing.
Option2 Isolation dampers shall be opposed blade low leakage design. The dampers shall be aluminum construction and coated to match the fan housing. 2-position, spring return actuators shall be provided. The actuator shall be pre-wired with appropriate transformer to the fan disconnect switch to open when the fan is energized and close via spring return when the fan is de-energized.
2.06 FAN MOTORS AND DRIVES
Option1 Fan motors shall be premium efficiency, NEMA frame, nominal 1800 or 3600 RPM Totally Enclosed Fan Cooled (TEFC) with a 1.15 service factor.
Option2 Fan motors shall be premium efficiency, NEMA frame, nominal 1800 or 3600 RPM Totally Enclosed Fan Cooled, Inverter Duty Labeled with a 1.15 service factor.
Option3 Fan motors shall be premium efficiency, NEMA frame, nominal 1800 or 3600 RPM Mill and Chem duty with a 1.15 service factor.
Option4 Fan motors shall be premium efficiency, NEMA frame, nominal 1800 or 3600 RPM Explosion Proof with 1.0 service factor. Class ___ and Division ___ Rating.
Option1 Belt driven fan drive belts shall be oil and heat resistant, static conducting. Fixed drives shall be sized for a minimum 1.5 service factor (150% of the motor horsepower) and shall be readily and easily accessible for service, if required.
Option2 Belt driven fan drive belts shall be oil and heat resistant, static conducting. Fixed drives shall be sized for a minimum 2.0 service factor (200% of the motor horsepower) and shall be readily and easily accessible for service, if required.
Belt driven fans shall utilize precision machined cast iron type sheaves, keyed and securely attached to the wheel and motor shafts.
PART 3 INSTALLATION
Install high plume fan system(s) as indicated on the contract drawings and in the contract specifications.
Install fan system(s) in accordance with manufacturers Installation, Operation, and Maintenance Manuals. Start up procedures from the IOM manuals shall be strictly followed.
PART 4 ACCEPTABLE MANUFACTURERS
LOREN COOK COMPANY, Model TCNHBLE